Fire pump testing in Maryland: the weekly run, the yearly flow test, and what the report has to show the fire marshal.
Fire pump testing in Maryland comes in two parts. A short run with no water flowing proves the pump starts by itself, and trained building staff or a service company does it through the year. A full flow test once a year measures the pump against its nameplate, and that written report is what the fire marshal asks to see.
Which buildings have a fire pump
A fire pump goes in when the public water cannot run the sprinkler system by itself. Tall buildings and high storage are the usual reasons, and so is a weak main at the end of a long street. That puts pumps in the office and apartment towers of Bethesda, Silver Spring, Towson and downtown Baltimore, in warehouses along the highway corridors in Howard and Anne Arundel, and in hospitals, hotels and large schools across the state.
Not sure whether your building has one? Look for a locked room near the sprinkler risers with a motor on a steel base, a tall control cabinet on the wall beside it, and a row of capped hose outlets on the outside wall. Text a photo of what is in that room to (240) 222-5257 and we will tell you what you are looking at.
The two tests, side by side
| Test | Who does it | What it proves |
|---|---|---|
| The run with no water flowing | Trained building staff or a service company | The pump starts by itself and runs without trouble |
| The yearly flow test | A sprinkler technician with flow test equipment | The pump still delivers the water and pressure on its nameplate |
The weekly run
Building engineers call it the weekly run or the churn test. The pump is started the way a fire would start it, by a drop in pressure at the controller, and it runs for a set time with no water going anywhere. Nothing is measured against a curve. The point is to see the pump start by itself and to catch small problems early.
How often this run is due depends on whether the pump is electric or diesel and on the edition of the standard the building is under. That interval has moved between editions, so the one that applies to your pump is the one written on your last test report. The person doing the run keeps a log, and the log should show these things each time.
- The date, the time and who ran it.
- The pressure at which the pump started, and that it started without help.
- The suction and discharge gauge readings while it ran.
- Anything odd, such as heavy leaking at the packing, noise, vibration or heat.
- On a diesel pump, the fuel level, the batteries and the engine gauges.
- That the controller was left in automatic when the run was over.
That last line matters most. A pump left in the off position after a test is a building with no fire pump, and nobody knows until the next person opens the door. See a controller switched to off, an alarm light on the cabinet or a pump that would not start on its run? Call or text (240) 222-5257 with a photo of the controller right then.
The yearly flow test
Once a year the pump has to move real water. Hoses or a flow meter are connected to the test header, and the pump is run at several flows, from no flow at all up past the flow it is rated for. At each point the technician writes down the flow, the suction pressure, the discharge pressure and the pump speed, plus the volts and amps on an electric motor.
Those points are plotted as a curve and laid over two others. One is the curve from the nameplate and the factory test. The second is last year’s result. A healthy pump lands on or close to both. The test also shows what the water supply feeding the pump is doing, because the suction gauge is read at every flow.
This test puts a lot of water on the ground and it takes planning. The alarm company is told, the discharge is aimed where it will not flood a garage or wash out a planting bed, and in a tight downtown lot in Baltimore City or Silver Spring the hoses may have to run to the street.
What a failing curve means
A curve that sits below the nameplate means the pump is giving the sprinkler system less water or less pressure than the design counted on. The cause is one of a short list.
- A worn pump. Impeller and wear ring clearances open up over the years and the pressure drops at every flow.
- A starved suction. A partly closed valve, a clogged strainer or a weaker street main shows up as suction pressure falling off as the flow goes up.
- A driver problem. An engine running below speed or a motor with a power problem turns the pump too slowly to make its numbers.
- A bad reading. A gauge out of calibration or a test header valve not fully open can fake a failure.
Call or text (240) 222-5257 with a photo of the failing report and the pump nameplate, and we will tell you which of these it looks like and what the repair involves. A pump that cannot meet its curve is a deficiency on the report, and a pump that will not start is an impairment. Howard County requires a fire watch for any system out of service or impaired for more than four hours, and Anne Arundel says the building is evacuated or a fire watch is set up whenever a required system fails or is impaired.
Controller and power checks
The pump is only as good as what starts it. On the yearly visit the controller is checked along with the pump.
- The pump starts at the pressure the controller is set for.
- The small pressure maintenance pump, called the jockey pump, starts first and stops by itself.
- The pump running, power loss and trouble signals reach the fire alarm panel.
- On an electric pump with a second power source, the transfer switch moves the pump over to it.
- On a diesel pump, both battery sets crank the engine and the fuel tank is kept filled.
- The relief valve and the cooling water line work while the pump runs.
A jockey pump that kicks on every few minutes is worth a call by itself. It means the system is losing pressure somewhere, through a leak or a check valve that is not holding. Text a short video of it cycling to (240) 222-5257 and we will tell you where we would look first.
The report and who gets it
The standard says a record is made of every inspection, test and maintenance job, and that the records are handed to the fire official on request. For a pump the yearly report should carry these.
- The nameplate data, with the make, model, rated flow, rated pressure and speed.
- Every reading taken at every flow point.
- The plotted curve, set against the nameplate and last year.
- The controller and alarm signal results.
- The technician’s name, company and credential, and the date.
- A list of findings, with the pump left in automatic noted at the end.
The owner keeps it. Howard County wants a copy of each report kept on the premises, and the company that did the work files it through the county’s contractor portal. Anne Arundel wants the documentation on hand when the Fire Marshal walks in, and it asks for copies of the annual pump test any time new sprinkler work ties into an existing pump. A tenant fit out in Glen Burnie or Annapolis can stall at plan review because nobody can find last year’s pump test.
Replacing a pump is not a maintenance item. Montgomery County makes every fire pump installation or replacement its own permit and submittal, and on our jobs the licensed sprinkler contractor on the job designs the work, installs it and pulls that permit. The rest of the yearly schedule for the building is in our guide to commercial sprinkler inspections.
Home systems on a well
A house on a well in Frederick, Howard or upper Montgomery County can have a sprinkler pump too, and it is a different animal. It is a small pump beside a storage tank, built to the home sprinkler standard, with none of the commercial test schedule above. It still gets checked at the annual inspection. Our guides on pump and tank replacement and on what happens to a pump fed system in a power outage cover the home side.
What to send us
- The address, the county and what the building is used for.
- A photo of the pump nameplate and the controller.
- The last yearly flow test report, or a note that nobody has it.
- The run log, if the building keeps one.
- Any notice or correction order from the fire marshal.
Call or text (240) 222-5257 with those and a photo of the pump room, and we will send a written quote for the flow test and any repairs. Pricing for the rest of our work is on the cost page. We test and repair fire pumps in Montgomery, Prince George’s, Baltimore County, Baltimore City, Anne Arundel, Howard and Frederick.
Pump test due, overdue or failed?
Call or text a photo of the pump nameplate and the last test report. We tell you what is due and send a written quote for the flow test and any repairs.
Call (240) 222-5257